I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams 
80 
  HC900 Hybrid Controller Installation and User Guide 
Revision 5 
  
9/03 
AC Output Module Wiring 
The AC Output Module provides eight output circuits.  Each output is isolated from the other outputs.  An 
example of AC output wiring is shown in Figure 45.  Specifications for this module and for other modules 
are given in the Specifications section of this manual. 
Output Loading  
Voltage: 85 to 240 Vac  
Maximum per output: 2.0A resistive load  
Maximum per module: 8.0A 
NOTE 
When exceeding 1.0 A per output, it is recommended (but not required) to connect the high-current loads to 
every other output - for example, outputs 1, 3, 5, 7 or 2, 4, 6, 8.  This distributes heat more evenly across 
the heat sink. 
Jumper Comb 
A ten-position jumper comb is available for inter-connecting all L1 (Hot) terminals (1, 3, 5, 7, 9, 11, 13, 15, 
17, 19).  See Figure 46. 
Replaceable Fuses 
Each output circuit on the AC Output Module includes a (plug-in) replaceable fuse.   
Replacement fuse is from Wickmann, part #3741315041. This is a 3.15 Amp time lag fuse with UL/CSA 
approval for 250 VAC.  
 
 
Hazardous voltages exist at terminal blocks. 
•  Using switches at field devices, disconnect the field wiring from power sources before servicing. 
Failure to comply with these instructions could result in death or serious injury.