Note: Function switch setting of LM ADAPTER is different according to the management item of the
equipment connected with L
ON
W
ORKS
®
. Carefully set the system.
SW1-1
ON
OFF
Function switch
of local prohibit
local prohibit effective
local prohibit invalidity
ON
OFF
LOSSNAY is operated
from L
ON
W
ORKS
®
 
LOSSNAY interlocks
with the indoor unit
Switch name
Function
OFF
Factory
setting
Operation local prohibit nv input from
L
ON
W
ORKS
®
 becomes Effective when switch is ON.
Operation local prohibit nv input from
L
ON
W
ORKS
®
 becomes invalid when switch is OFF.
Note
SW1-5 Function switch
of LOSSNAY
SW1-7 Function switch
of SNVT_switch
OFF
Please turn on the switch when LOSSNAY
is operation from L
ON
W
ORKS
®
.
Please turn off the switch when LOSSNAY
interlocks with the indoor units.
ON
OFF
Enable forced thermo OFF
Disable forced thermo OFF
SW1-8 Select enable/
disable forced
thermo OFF
OFF
When “ON”, the forced thermo OFF nv 
input/output are enabled.
When “OFF”, the forced thermo OFF nv 
input/output are disabled.
Before power 
supply
Before power 
supply
ON
OFF
Enable
Disable 
SW1-4 Reset filter sign/
Select enable/
disable operation 
duration
OFF
Before power 
supply
Before power 
supply
Before power 
supply
Before power 
supply
ON
OFF
ON(test run) is transmitted
to the indoor units
OFF is transmitted and
indoor units stop test run
SW1-9 Indoor units
test run switch
OFF
Always
ON
OFF
Connected cancellation
command is transmitted
to the indoor units
None
SW3-2 Initialization
switch of air
conditioner units
OFF
Always
SW1-3
ON
OFF
Indoor temperature
state interval switch
Transmission interval
 (1minutes or more)
Transmission interval
 (10 minutes or more)
OFF
SW1-2
ON
OFF
Used together with
system controller switch
used together with system controller
not used together with system controller
OFF
Set timing
SW
 *number of indoor units that should
  be connected is 30 or less
When “ON”, the reset filter sign input and the
operation duration output are enabled.
When “OFF”, the reset filter sign input and 
the operation duration output are disabled.
ON
OFF
SNVT Standard
Original
OFF
Before power 
supply
When “ON”, the specifications of the nv using
the SNVT_switch comply with the SNVT Standards.
When “OFF”, the nv using the SNVT_switch 
has original specifications.
LED001 , LED002
LED003 , LED004
(                            )
LON connection terminal
Neuron Chip
[ LM ADAPTER Main Circuit Board (L.B) ]
LON LED
(LED502)
M-NET address switch
(Factory setting: 47)
Maintenance LED
Function selection switch
(Factory setting: All OFF)
CPU power supply LED
(LED009)
M-NET LED
(LED201)
LON transceiver: FTT-10A
CN 41
M-NET transmission 
power supply off
(Factory setting)
CN 40
M-NET transmission 
power supply on
Power supply LED
(LED402)
Host CPU
EPROM
(Program ID)
Neuron ID
Explanation of function switch