(1)The LM ADAPTER is not completely 
initialized. 
(2)Setting on M-NET side is not properly 
completed.
(3)If system controller is used together 
LM ADAPTER is not registered to 
system controller.
Turn OFF all SW2.  After verifying that LED002 is 
OFF, test the operation again.
 
Verify that the test operation of the air conditioner is 
properly completed.  Verify that M-NET transmission 
line is properly connected.
In system controller, register LM ADAPTER as the 
sub system controller.
Error content
Cause
Checking method and remedy
(1)The LM ADAPTER is not completely 
initialized. 
(2)Setting on M-NET side is not properly 
completed.
(3)If system controller is used in 
combination, LM ADAPTER is not 
registered to system controller.
(4)The independent/combined 
LOSSNAY of LM ADAPTER is not 
set.
Refer to 2-(1).
Refer to 2-(2).
Refer to 2-(3).
Turn on SW1-5 of LM ADAPTER, and reset the 
power supply.
(1)The LM ADAPTER is not completely 
initialized. 
(2)Setting on M-NET side is not properly 
completed.
(3)If system controller is used in 
combination, LM ADAPTER is not 
registered to system controller.
(4)L
ON
W
ORKS
®
 network transmission 
line is not properly connected.
(5)The termination of L
ON
W
ORKS
®
 
network is not properly set.
(6) Binding of L
ON
W
ORKS
®
 network is 
not properly ended.
Refer to 2-(1).
Refer to 2-(2).
Refer to 2-(3).
Check for disconnection on TB21, short-circuit and 
wire breakage on the network wire and so on.
Verify that the termination of L
ON
W
ORKS
®
 network is 
properly set according to the system design.
Apply the binding again.
Even if it is operated 
with the remote 
controller/system 
controller, it is not 
informed to the host 
on LON side.
2
1
No.
3
4
LED002 is ON
(1) It takes time for the initial processing 
     to complete (normal).
(2)Setting on M-NET side is not properly 
    completed.
(3) M-NET power supply switch has not 
     been set.
(4) The power supply to the air conditio-
     ner unit is disconnected.
It can take about 15 minutes for the initial processing 
to complete. Wait until the initial processing finishes.
Verify that the test operation of the air conditioner is 
properly completed.  Verify that M-NET transmission 
line is properly connected.
Follow the instructions in “4. System Setting” and 
check the power supply unit setting, and the LM 
ADAPTER power supply switch connector setting.
Verify that the air conditioner unit power supply is 
not disconnected.
* Use a tester to check the voltage of the terminal 
  (TB2). DC17-30 V
The air conditioner 
unit does not operate 
even by performing 
a test run using the 
LM ADAPTER’S switch 
SW1-9. 
The LOSSNAY unit 
does not operate 
even by performing 
a test run using the 
LM ADAPTER’S 
switch SW1-9. 
6-2 Troubleshooting