3.3  Logs
3.3.1  Measurements
Click on the “Measurements” section in the menu.
The following measurements are saved and time-stamped:
“Input voltage”: Value of the utility voltage supplying your UPS (average of 3 phases for UPS' equipped
with a 3-phase input) 
“Input frequency”: Value of the utility frequency feeding your UPS 
“Output voltage”: Value of the output voltage of your UPS (average of the 3 phases for UPS’ with a 3-
phase output) 
“Output load”: Value of the percentage of load at UPS output (Value of the most loaded phase for 3-phase
UPS’) 
“ Output current Ph x”: Value of the output current for each phase on three-phase UPSs
“Battery capacity”: Percentage of charge available in the battery 
“Remaining time”: Estimation of the remaining backup time 
The save frequency of these values is defined in the “System” page (60 seconds by default).
Approximately 1000 time-stamps are stored permanently on the card. The oldest time-stamps are
automatically deleted.
“Save” enables all saved values to be opened or saved in CSV format (compatible with Excel type
spreadsheets)
“Clear” enables deletion of all records. The administrator must enter his login / password to validate this
action if he has not already done so during the current session.