Multi-Tech Systems 7600 사용자 설명서

다운로드
페이지 372
The Front Panel’s Setup Menu
 ION 7500 / ION 7600 User’s Guide
Page 32
Chapter 2 - Using The Front Panel 
Using the Front Panel Buttons for Configuration
Use the front panel buttons as follows to adjust the settings:
PROG
Press the 
PROG
 (programming) button to access the Setup Menu. Once in 
programming mode, the 
PROG
 button functions just like an Enter key on a 
computer keyboard. Press the 
PROG
 button to select a highlighted item or accept 
changes, passwords, and trigger resets.
ESC
Press the 
ESC
 (escape) button to return to a higher menu or abort a configuration 
change.
Navigation
Highlight menu items with the vertical (Up/Down) buttons.
Entering numbers: when a digit is highlighted, pressing the Up button increments 
the number by one, and pressing the Down button decreases it. Move the cursor to 
an adjacent digit with the horizontal (Left/Right) buttons.
Softkeys
Press a Softkey button when Softkey options become available (when titles appear 
in the Softkey title bar). Use Softkeys to select the parameters that you want to 
configure from the various sub-menus.
Passwords
All configuration functions in the front panel are password protected. The 
password is set to 0 (zero) in the factory. This password allows you to access the 
Security setup menu and to disable or change the password for a custom value. 
The front panel only prompts you for the meter password before you make your 
first configuration change. 
Setup Mode Timeout
Once the meter has been configured, the front panel automatically exits the Setup 
menu five minutes after the last button press is detected. If the front panel returns 
to data display mode, you must re-enter the Setup menu and provide the valid 
meter password to resume making configuration changes.
Confirming Configuration Changes
The CONFIRM screen appears whenever you attempt to change the meter’s 
settings through the front panel. This allows you to abort an unwanted 
configuration change. The front panel also informs you when an entry is out of 
range. In either case, you must press the 
PROG
 button to return to the setup screen.
WRITING
 
ERROR
 Screen
If the CONFIRM screen does not appear for a valid entry, or the display reports a 
WRITING ERROR, repeat the configuration change. If the problem persists, 
contact Technical Services.
PROG
ESC
ESC TO CANCEL
PROG TO CONFIRM
CONFIRM