MGC+ Hardware and Installation Manual
2-33
Connecting to the Power Source
To connect to the AC Inlet:
1.
Make sure that the power switch located on the rear panel of the MGC+ 
unit is off.
2.
Insert the power cable into the power connector on the rear panel of the 
MGC+50 unit.
3.
Insert the power cable into the power source socket.
4.
Turn on the power by pressing on the power switch located on the rear 
panel of the MGC+50 unit.
If the unit is rack mounted, the single-point ground on the MCU-50 must 
be connected to the rack with a single conductor and attached so that it 
prevents loosening.
The following restrictions apply to the conductors and connectors that 
may be used to ground the unit when rack mounted:
When using bare conductors, they must be coated with an 
appropriate antioxidant compound before crimp connections are 
made. Tinned, solder-plated or silver plated connectors do not have 
to be prepared in this manner.
Multiple connectors should not be secured with the same bolt 
assemblies.
Listed fastening hardware must be compatible with the materials 
being joined and must avoid loosening, deterioration and 
electrochemical corrosion of the hardware and joint materials.
AC Inlet
Main Switch