Use the inverter under the following environmental conditions: 
 
Ambient 
temperature 
- 10 ~ 40 ℃  (non-freezing) 
Relative 
humidity 
90% RH or less (non-condensing) 
Storage 
temperature 
- 20 ~ 65 ℃ 
Location 
Protected from corrosive gas, combustible gas, oil mist or dust 
Altitude, 
Vibration 
Max. 1,000m above sea level, Max. 5.9m/sec
2
 (0.6G)  
or less 
Environ
m
ent
 
Atmospheric 
pressure 
70 ~ 106 kPa 
      
 
(2) Wiring 
 
 
Do not connect a power factor correction capacitor, surge suppressor, or RFI filter to the output of the inverter. 
 
The connection orientation of the output cables U, V, W to the motor will affect the direction of rotation of the 
motor. 
 
Incorrect terminal wiring could result in the equipment damage. 
 
Reversing the polarity (+/-) of the terminals could damage the inverter. 
 
Only authorized personnel familiar with CMC inverter should perform wiring and inspections. 
 
Always install the inverter before wiring. Otherwise, you may get an electric shock or have bodily injury. 
 
(3) Trial run 
 
 
Check all parameters during operation. Changing parameter values might be required depending on the load.  
 
Always apply permissible range of voltage to the each terminal as indicated in this manual. Otherwise, it could 
lead to inverter damage. 
 
 
(4) Operation precautions 
 
 
When the Auto restart function is selected, stay away from the equipment as a motor will restart suddenly after 
an alarm stop.   
 
The Stop key on the keypad is valid only when the appropriate function setting has been made. Prepare an 
emergency stop switch separately. 
 
If an alarm reset is made with the reference signal present, a sudden start will occur. Check that the reference 
signal is turned off in advance. Otherwise an accident could occur. 
 
Do not modify or alter anything inside the inverter. 
 
Motor might not be protected by electronic thermal function of inverter. 
 
Do not use a magnetic contactor on the inverter input for frequent starting/stopping of the inverter.  
 
Use a noise filter to reduce the effect of electromagnetic interference. Otherwise nearby electronic equipment 
may be affected.  
 
In case of input voltage unbalance, install AC reactor. Power Factor capacitors and generators may become 
overheated and damaged due to potential high frequency noise transmitted from inverter.