External Connection - Connecting the UPS
20
AIS 5000 400V Installation Manual
990-2440
Terminals.
Torque specifications.
Grounding
System grounding:
Grounding busbar marked “Grounding” must be connected by grounding electrode conductor to a
local grounding electrode. Grounding electrode conductor to be supplied by the customer. (See
grounding busbar on illustrations starting on page 17).
Grounding busbar marked “Grounding” must be connected by grounding electrode conductor to a
local grounding electrode. Grounding electrode conductor to be supplied by the customer. (See
grounding busbar on illustrations starting on page 17).
Input X001/Output
X004/Bypass Input
X090
Battery Q004
Protective Earth
PE
10 kVA
M6
Direct on breaker
terminals
Direct on Earth Busbar
20 kVA
M6
Direct on breaker
terminals
Direct on Earth Busbar
30 kVA
M6
Direct on breaker
terminals
Direct on Earth Busbar
40 kVA
M8
Direct on breaker
terminals
Direct on Earth Busbar
60 kVA
M8
Direct on breaker
terminals
Direct on Earth Busbar
80 kVA
M10
Direct on breaker
terminals
Direct on Earth Busbar
100 kVA
M10
Direct on breaker
terminals
Direct on Earth Busbar
Note
The UPS input / bypass input is 4-Wire + Ground.
Stud size
6 mm
8 mm
10 mm
12 mm
Torque
66/7.5 lb-in/Nm
133/15 lb-in/Nm
266/30 lb-in/Nm
443/50 lb-in/Nm