American Power Conversion AIS 5000 사용자 설명서

다운로드
페이지 82
40
AIS 5000 400V Installation Manual
990-2440
60kVA 400V UPS
IS60KH
Performance - Linear Load
DC to AC Efficiency [%]
92.6
AC to AC Efficiency [%]
87.9
Heat Dissipation [BTU/h] [W]
22,338/6,541
Electrical Input
Mains
Voltage
400 V 3 Wire + G
P Nom.
54.42 kW
I Nom. 
(Nominal input current based on nominal mains 
voltage and batteries fully charged at 100% ohmic 
load)
90.08 A
I Max.
(Maximum input current based on full battery 
recharge and nominal mains voltage at 100% ohmic 
load)
117 A
Over-Current protection [A]
(Based on continuous full load)
125 A
Input Voltage Range
+ 10%, -15% programmable
Input Frequency
50 Hz + 6% programmable
Current Distortion
< 12%
Power Factor
0.8 - 0.9
Bypass
Voltage
400 V 3 Wire + N + G
I Nom
86.6 A
Over-Current protection [A]
(Based on continuous full load)
90 A
Bypass Voltage Range
+ 10% programmable
Electrical Output
Voltage
400 V 3 Wire + N + G
Nominal current 
(The output current is based on the nominal apparent 
power of the UPS)
86.6 A
Frequency Range
50Hz (adjustable 0.25, 0.50, 1-8%)