American Power Conversion AIS 5000 사용자 설명서

다운로드
페이지 82
48
AIS 5000 400V Installation Manual
990-2440
100kVA 400V UPS
IS100KH
Performance - Linear Load
DC to AC Efficiency [%]
90.7
AC to AC Efficiency [%]
87.5
Heat Dissipation [BTU/h] [W]
38,745/11,345
Electrical Input
Mains
Voltage
400 V 3 Wire + G
P Nom.
90.67 kW
I Nom. 
(Nominal input current based on nominal mains 
voltage and batteries fully charged at 100% ohmic 
load)
146.38 A
I Max.
(Maximum input current based on full battery 
recharge and nominal mains voltage at 100% ohmic 
load)
193.9 A
Over-Current protection [A]
(Based on continuous full load)
200 A
Input Voltage Range
+ 10%, -15% programmable
Input Frequency
50 Hz + 6% programmable
Current Distortion
< 12%
Power Factor
0.8 - 0.9
Bypass
Voltage
400 V 3 Wire + N + G
I Nom
144.3 A
Over-Current protection [A]
(Based on continuous full load)
160 A
Bypass Voltage Range
+ 10% programmable
Electrical Output
Voltage
400 V 3 Wire + N + G
Nominal current 
(The output current is based on the nominal apparent 
power of the UPS)
144.3 A
Frequency Range
50Hz (0.25, 0.50, 1-8%)