Emerson MODBUS IP 사용자 설명서
Modbus 485 and Modbus IP Protocols - UPS Systems
139
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 50
Liebert Nfinity
®
- Status and Coil
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
Automatic Battery Test Enabled
10003
3
1
—
—
Battery Charger On
10044
—
1
—
—
Inverter Ready
10047
—
1
—
—
Power Factor Correction State
10050
—
1
—
—
Load on Inverter
10073
—
1
—
—
Bypass Active
10074
—
1
—
—
Replace Battery
10081
—
1
—
—
Battery Under Test
10082
—
1
—
—
Load on Battery
10128
—
1
—
—
Load on Bypass
10129
—
1
—
—
Load on Manual Bypass
10132
—
1
—
—
Load Transferred to Bypass Due to UPS Fault
10134
—
1
—
—
Transfer Inhibit
10146
—
1
—
—
Output Off Pending
10151
—
1
—
—
Low Battery - Shutdown Imminent
10152
—
1
—
—
Output Overload
10154
—
1
—
—
UPS Overload
10155
—
1
—
—
Output Off
10158
—
1
—
—
Check Air Filter - Replace
10170
—
1
—
—
Transformer Over Temperature
10178
—
1
—
—
Input Power Supply Fail
10186
—
1
—
—
Internal Device Communication Failure
10284
—
1
—
—
Device Active Alarm
10290
—
1
—
—
Main Control Warning
10291
—
1
—
—
Redundant Control Warning
10292
—
1
—
—
Control Module Failure
10293
—
1
—
—
Redundant Control Module Failed
10294
—
1
—
—
User Interface Module Failed
10295
—
1
—
—
UPS Power Not Redundant
10296
—
1
—
—
Power Module Failure
10298
—
1
—
—
Battery Module Failure
10299
—
1
—
—
Power Module Warning
10300
—
1
—
—
Battery Module Warning
10301
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.