4. TECHNICAL CHARACTERISTICS
GEK-106168E
DBF Breaker Failure Protection
21
4.  
4.  
4.  
4.  
TECHNICAL CHARACTERISTICS
TECHNICAL CHARACTERISTICS
TECHNICAL CHARACTERISTICS
TECHNICAL CHARACTERISTICS
4.1. MODEL LIST
Position
DBF
1
-
-
-
-
1
1
-
-
0
0
A
Description
Comm. Interface
0
P2: RS232 + P3: RS232
5
1
P2: RS232 + P3: Plastic F.O.
2
P2: RS232 + P3: Glass F.O.
3
P2: RS232 + P3: RS485
6
Ranges
[[[[
1
]]]]
See Table
[
1R
]
Comm. Protocols
7
1
P1, P2, P3: Mlink
2
P1, P2: Mlink; P3: ModBus
Language
8
M
Spanish
D
English
Model
11
0
Basic Model
1
Enhanced Model (Expansion
board)
Power Supply
12
G
48-125 VDC
H
110-250 VDC
13,14
0
0
Special Models
15
A
Revision
TABLE
[[[[
1R
]]]]
- RANGES
MODELS
A
B
C
D
E
F
G
DBF
PHASE
1-12 A
0.2-2.4 A
1-12A
1-12 A
1-12 A
0.5-6 A
0.5-6 A
GROUND
1-12 A
0.2-2.4 A
0.2-2.4 A
0.5-6 A
0.1-1.2 A
0.2-2.4 A
0.1-1.2 A
4.1.1. SPECIAL MODELS
The input voltage of the standard model corresponds to the Power Supply voltage. The following models have
been developed to allow the selection of an input voltage independently of the Power Supply.
The following codes should be placed as two last digits before in the ordering code for selecting the desired
characteristics:
MOD 04:
V inputs: 48 Vdc
±
20%
MOD 05:
V inputs: 110 Vdc
±
20%
MOD 06:
V inputs: 125 Vdc
±
20%
MOD 07:
V inputs: 250 Vdc
±
20%
Example: If we want to order a relay model with a digital input voltage of 48 Vdc, the model should be:
DBF1*****11**04A.