Fluke 1743 사용자 설명서
![Fluke](https://files.manualsbrain.com/attachments/9d57315a76f85bd9af23da46bf7ecaf7f248b87d/common/fit/150/50/7671c6748e9e70e4c5afb082a772388950496a1161e6cfdedf4b942e284b/brand_logo.png)
Power Quality Logger
Methods of Logging
31
Voltage Interruptions
The Logger records two types of interruptions:
•
All measured RMS values of input voltages that are < 1% of the
nominal voltage. (This threshold can be adjusted in PQ Log.)
•
Interruptions > 10 ms (0.5 line power periods).
The start time and duration of each interruption are registered.
Time
90% Un
1%
Duration
100% Un
110% Un
egb018.eps