Chapter 6 Fault Code Information and Maintenance|  
Revision August 2008, 2ELE, V1.02 
6-5
6.1.2 Reset 
There are three methods to reset the AC motor drive after solving the fault: 
1. Press 
 key on keypad. 
2. 
Set external terminal to “RESET” (set one of Pr.04.05~Pr.04.08 to 05) and then set to be 
ON. 
3. Send 
“RESET” 
command by communication. 
NOTE
  
Make sure that RUN command or signal is OFF before executing RESET to prevent damage or 
personal injury due to immediate operation. 
 
6.2 Maintenance and Inspections 
Modern AC motor drives are based on solid-state electronics technology. Preventive maintenance is 
required to keep the AC motor drive in its optimal condition, and to ensure a long life. It is 
recommended to have a qualified technician perform a check-up of the AC motor drive regularly. 
 
Daily Inspection: 
Basic check-up items to detect if there were any abnormalities during operation are: 
 
1. 
Whether the motors are operating as expected. 
2. 
Whether the installation environment is abnormal. 
3. 
Whether the cooling system is operating as expected. 
4. 
Whether any irregular vibration or sound occurred during operation. 
5. 
Whether the motors are overheating during operation. 
6. 
Always check the input voltage of the AC drive with a Voltmeter. 
 
Periodic Inspection:
 
Before the check-up, always turn off the AC input power and remove the cover. Wait at least 10 
minutes after all display lamps have gone out, and then confirm that the capacitors have fully 
discharged by measuring the voltage between 
 ~ 
. It should be less than 25VDC.