Delta Electronics VFD-EL 사용자 설명서

다운로드
페이지 209
Appendix B  Accessories|  
B-22 
Revision August 2008, 2ELE, V1.02
 
Communication 
Process Data Objects 
(PDO) 
Service Data Object 
(SDO) 
Synchronization 
(SYNC) 
Emergency (EMCY) 
Message type 
Network Management 
(NMT) 
Baud 
rate 
10 Kbps 
20 Kbps 
50 Kbps 
125 Kbps 
250 Kbps 
500 Kbps 
800 Kbps 
1 Mbps 
Product code 
Delta VFD-EL AC motor drive    22 
Device type 
402 
Vendor ID 
477 
Environmental Specifications 
Noise Immunity 
ESD(IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
EFT(IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV, 
Analog & Communication I/O: 1KV 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS(IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m 
Environment 
Operation: 0°C ~ 55°C (Temperature), 50 ~ 95% (Humidity), Pollution 
degree 2;  
Storage: -40°C ~ 70°C (Temperature), 5 ~ 95% (Humidity) 
Vibration / 
Shock 
Resistance 
Standard: IEC1131-2, IEC 68-2-6(TEST Fc/IEC1131-2 & IEC 68-2-27 
(TEST Ea) 
Certifications 
Standard: IEC 61131-2,UL508 
B.8.4.3 Components 
Pin Definition on CANopen Connection Port 
To connect with CANopen, use the connector enclosed with CME-COP01 or any connectors 
you can buy in the store for wiring. 
Pin 
Signal 
Content 
CAN_GND 
Ground / 0 V / V-
2 CAN_L 
Signal- 
3 SHIELD 
Shield 
4 CAN_H  Signal+ 
5 -  Reserved 
 
1  2  3  4  5 
Baud Rate Setting 
Rotary switch (BR) sets up the communication speed on 
CANopen network in hex. Setup range: 0 ~ 7 (8 ~F are 
forbidden)
  
01
2
3
4
5
6
7 8 9 A
B
C
D
EF
BR