2.3 Main Circuit 
2.3.1 Main Circuit Connection 
 
R(L1)
S(L2)
T(L3)
R
S
T
U(T 1)
V(T2)
W(T3)
IM
3~
MC
E
E
+
-
No fuse breaker
         (NFB)
Brake Resistor(Optional)
Motor
BUE
BR
Brake Unit
(Optional)
 
 
 
Terminal Symbol 
Explanation of Terminal Function 
R/L1, S/L2, T/L3 
AC line input terminals (1-phase/3-phase) 
U/T1, V/T2, W/T3 
AC drive output terminals for connecting 3-phase induction motor 
+, - 
Connections for External Brake unit (BUE series) 
 
Earth connection, please comply with local regulations. 
 
CAUTION!
 
Mains power terminals (R/L1, S/L2, T/L3) 
„ 
Connect these terminals (R/L1, S/L2, T/L3) via a non-fuse breaker or earth leakage 
breaker to 3-phase AC power (some models to 1-phase AC power) for circuit protection. It 
is unnecessary to consider phase-sequence. 
„ 
It is recommended to add a magnetic contactor (MC) in the power input wiring to cut off 
power quickly and reduce malfunction when activating the protection function of AC motor 
drives. Both ends of the MC should have an R-C surge absorber. 
„ 
Please make sure to fasten the screw of the main circuit terminals to prevent sparks 
which is made by the loose screws due to vibration.