4.2 Parameter Settings for Applications 
Speed Search 
Applications Purpose 
Functions 
Related 
Parameters
Windmill, winding 
machine, fan and all 
inertia loads 
Restart free-
running motor 
Before the free-running motor is 
completely stopped, it can be restarted 
without detection of motor speed. The 
AC motor drive will auto search motor 
speed and will accelerate when its 
speed is the same as the motor speed.
08.04~08.08
 
DC Brake before Running 
Applications Purpose 
Functions 
Related 
Parameters
When e.g. windmills, 
fans and pumps rotate 
freely by wind or flow 
without applying power 
Keep the free-
running motor at 
standstill. 
If the running direction of the free-
running motor is not steady, please 
execute DC brake before start-up. 
08.00 
08.01 
 
Energy Saving 
Applications Purpose 
Functions 
Related 
Parameters
Punching machines 
fans, pumps and 
precision machinery 
Energy saving and 
less vibrations 
Energy saving when the AC motor 
drive runs at constant speed, yet full 
power acceleration and deceleration 
For precision machinery it also helps 
to lower vibrations. 
08.17 
 
Multi-step Operation 
Applications Purpose 
Functions 
Related 
Parameters
Conveying machinery 
Cyclic operation by 
multi-step speeds.
To control 15-step speeds and duration 
by simple contact signals. 
04.05~04.08
05.00~05.14
 
Switching acceleration and deceleration times 
Applications Purpose 
Functions 
Related 
Parameters
Auto turntable for 
conveying machinery 
Switching 
acceleration and 
deceleration times 
by external signal
When an AC motor drive drives two or 
more motors, it can reach high-speed 
but still start and stop smoothly. 
01.09~01.12
04.05~04.08