2. For Proper Operation 
 
2.1 Input Power Requirements 
(1)  Please use UPS as a commercial power supply in the region and the output voltage of UPS 
are matched referring to the table below. 
 
MODEL 
AC input voltage 
AC input frequency 
NOTE 
E11A202U001 
120V (+15%,-20%) 
50 or 60Hz (±5%) 
 
E11A202U001J 
100,110,115,120V (+15%,-20%) 
50 or 60Hz (±5%) 
 
 
※ 
The frequency variation range is set to 
±3% when the UPS is shipped from the factory.   
If the frequency variation range of input power supply is 
±5%, select ±5% as described in item 
  “Frequency sync range” of §10.1 “Setup Menu Item List”. An input power error occurs when 
the frequency sync range exceeds the setting value, preventing the UPS from switching to 
inverter operation. 
(2)  The current capacity of the AC power supply must satisfy the requirements of the UPS   
(It is different depending on the model.) 
 
MODEL 
Input capacity 
Recommended capacity of breaker 
E11A202U001 
1.8kVA 
20A or more (Demand of UL rules) 
E11A202U001J 
1.8kVA 
30A or more (Demand of UL rules) * 
 
*NOTE: Please set up Branch circuit protector of 30A in the switchboard for E11A202U001J. 
In branch circuit protector, please protect two poles of the ac input. (Demand of UL rules) 
 
2.2 Installation Precautions 
* Installation must be in accordance with the National Electric Code Articles 110-17 and 110-18. 
(1) Carefully consider the leakage current when a leakage circuit breaker is installed on the 
input side. The maximum leakage current of the UPS is 3mA. 
(2)  Keep the UPS at least 1 m (about 40 inches) away from CRT displays. Other devices which 
may be sensitive to magnetic flux should be kept away from the UPS, as it emits a slight 
amount of magnetic flux. 
(3) The UPS employs a fan for forced-air cooling. Provide at least 20 cm (about 8 inches) 
clearance at the front and back of the UPS to permit free airflow at the air intake and 
exhaust vents. Also, for maintenance purposes, a space of at least 1 m (about 40 inches) will 
be needed at the front of the UPS and a space of at least 50 cm (about 20 inches) will be 
needed at the back of the UPS. 
When mounting the UPS in a rack, use a rack which allows ventilation and provide at least 
20 cm (about 8 inches) clearance from the front and back of the rack to permit free airflow at 
the air intake and exhaust vents. Also, for maintenance purposes, a space of at least 1 m 
(about 40 inches) will be needed at the front of the rack, and a space of at least 50 cm (about 
20 inches) will be needed at the back of the rack. 
For details, see §6.3 “Installation Space”. 
(4)  When the AC input power is single-wire grounded, always connect the ground phase to the S 
terminal (phase) side on the UPS. 
(5) As far as possible, do not ground the output (load) side. If you must make a single-wire 
grounded connection, always connect the ground phase to the V terminal (phase) side on the 
UPS. (This is to prevent short-circuiting by the ground.) 
 
 
2.3 Usage Precautions 
(1)  Never short-circuit the output terminals, or connect a load which draws short-circuit current. 
Doing so causes protective functions to activate or the circuit breakers to trip, preventing 
output. 
(2)  Unsuitable load devices 
Do not connect laser printers, plain paper fax machines, copy machines, or overhead 
projectors as load devices. Such devices typically include heating elements that draw high 
current. This may cause an overload that could prevent battery backup operation when an 
outage occurs, and could damage the UPS.