Energiefluss bei gestörtem Netz 
Power circuit with faulty mains supply 
Handumgehungspfad 
Manual bypass path 
Netz Mains 
GR REC 
EUE SBS 
WR INV 
Netzeingangssicherungsautomat 
Mains input miniature circuit breaker 
Lade GR 
Load REC 
Handumgehung Manual 
bypass 
Gesicherte Schiene 
Secured busbar 
Schematische Darstellung 
Schematic diagram 
Batterie Battery 
Verbraucher Load 
 
The mains is not within the required tolerance range or has 
failed. In this case, power is supplied to the inverter from the 
charged battery without interruption. The power supply to the 
loads is therefore also ensured in the event of a mains failure. 
This drains the capacity of the battery and it is discharged. This 
status is signalled by the battery symbol lighting up (Battery 
LED), as well as an intermittent acoustic signal, at first every 4 
seconds and then every second shortly before switching off. 
The initial alarm can be suppressed by pressing the “Alarm off” 
button. The alarm is automatically reactivated when the battery 
capacity decreases. Depending on the expansion level, age 
and condition of the battery and in particular on the load to be 
supplied, the standby time can vary from a few minutes to 
several hours. 
The inverter is switched off if the battery voltage drops below a 
factory-set minimum voltage value.  
 
 
Never store the unit in this condition! The discharged battery 
system should be recharged within a week at the latest. 
When the voltage and frequency are within the tolerance range 
again after the mains is restored, the rectifiers switch back on