AEG Protect 1.1 사용자 설명서

다운로드
페이지 61
35
5.5.2
Connection of the Battery Cubicle PROTECT 1. BP20
Fig.: Rear view of the PROTECT 1.BP20 with cover removed.
The  battery  cubicle  is  supplied  with  a  separate  battery  string 
and separately enclosed battery fuses for safety and transport 
protection  reasons. 
Please  also  note  the  separate 
documentation enclosed with the battery cubicle. 
After  the  battery  cubicle  has  been  removed  from  the  pallet, 
first  remove  the  rear  cover.  Now  create  the  electrical 
connections  with  the  enclosed  connectors  (see  also  circuit 
diagram X1/X2/X3)   and 
The  PROTECT  1.100  is  connected  to  the  UPS  at  the  socket 
  using  the  special  battery  connection  cable  enclosed  with 
the  UPS,  and  in  the  case  of  the  PROTECT  1.150  or
PROTECT 1.200 with the battery connection cables enclosed 
with the battery cubicle at the terminals. Make sure to observe 
the terminal block assignment concerning the correct  polarity 
"+"  and  "-"  as  well  as  an  earth-fault-  and  short-circuit-proof 
routing,  in  addition  to  the  proper  earthing  of  the  battery 
cubicle.