Battery 
Autonomy time
  (for a battery charged 100% and at 25°C)
 
Autonomy time (nominal load, pf = 0.9 lag.) 
Linked 
battery modules 
D.
 
1000 D.
 
1500 D.
 
2000 D.
 
3000 
With integrated battery 
 
6 min. 
  5.5 min. 
 
6 min. 
  3.5 min. 
1 extra battery module 
  31 min. 
  25 min. 
  33 min. 
  18 min. 
2 extra battery modules    51 min. 
  46 min. 
  59 min. 
  34 min. 
3 extra battery modules    82 min. 
  69 min. 
  88 min. 
  53 min. 
4 extra battery modules    100 min. 
  90 min. 
  119 min. 
  69 min. 
 
Rated direct voltage (intermediate circuit) 
 
PROTECT D.
 
1000 
   36 V 
PROTECT D.
 
1500 48 
PROTECT D.
 
2000 
   72 V 
PROTECT D.
 
3000 72 
Float voltage 
2.28 Vdc/cell (pre-set to 25°C) 
 
charging voltage temperature dependent 
Setting range 
2.21 Vdc/cell – 2.31 Vdc/cell 
 
in 0.01V increments 
Batt.-charge power (max.)  1.4 Adc (PROTECT D.1000 / D.1500)
 
1.7 Adc (PROTECT D.2000 / D.3000)
 
Battery type 
Valve regulated lead battery (VRLA) 
 
Special type for high-current discharge 
PROTECT D.1000 
3 blocks at 12V 9Ah 
PROTECT D.1000 BP 
2 belts at 3 blocks at 12V 9Ah 
PROTECT D.1500 
4 blocks at 12V 9Ah 
PROTECT D.1500 BP 
2 belts at 4 blocks at 12V 9Ah 
PROTECT D.2000 
6 blocks at 12V 9Ah 
PROTECT D.3000 
6 blocks at 12V 9Ah 
PROTECT D.2030 BP 
2 belts at 6 blocks at 12V 9Ah 
Recharging times 
~ 3h to 90% for internal battery 
~9h
 
/
 
~15h
 
/
 
~21h
 
/
 
~27h with 1
 
/
 
2
 
/ 3 / 4 battery extension(s)