Liebert NXL 사용자 설명서

다운로드
페이지 20
Mechanical Installation
3
1.4.1 Moving the Cabinets
The Liebert NXL Input/Output Cabinet can be handled with a forklift or similar equipment.
When moving the unit by forklift, care must be taken to protect the panels. Do not exceed a 15-degree 
tilt with the forklift. Bottom structure will support the unit only if the forks are completely beneath 
the unit.
Handling the cabinet with straps is not authorized.
1.4.2 Clearances
Clearance around the front of the equipment should be sufficient to enable free passage of personnel 
with the doors fully open. Installation must leave a distance of 24" (610mm) between the top of the 
cabinet and any overhead obstacles to permit adequate circulation of air coming out of the unit.
Space must be reserved on the left side of the I/O cabinet. The UPS Rectifier/Inverter cabinet can be 
mounted only on the left side of the I/O cabinet.
1.4.3 Floor Installation/Anchoring
If the equipment is to be located on a raised floor, it should be mounted on a pedestal designed to 
accept the equipment point loading. Refer to the base view to design this pedestal.