DEFINITIONS FOR ILLUMINATED LED INDICATORS 
 
 
Power 
ON 
Site 
Wiring 
Fault 
 
Circuit 
Breaker 
 
Alarm 
CONDITION 
On Off Set Off 
 
Normal Mode 
 
Off On/Off Set 
Two 
Beeps 
 
Utility Failure- 
the UPS is in the battery 
mode. 
 
Off On/Off Set 
Rapid 
Beeps 
 
Utility Failure-
 The UPS is in the battery 
mode and will run out of battery-power shortly. 
 
Off Off Up 
Two 
Beeps 
or        
Rapid 
Beeps 
 
System Overload- 
Occurs when connected 
equipment exceeds the rating of UPS.  Turn 
the UPS off, unplug at least one piece of 
equipment, wait 10-seconds, reset the circuit 
breaker and turn the UPS on. 
Off On/Off Set 
Long 
Beep 
 
Battery Overload-
 Occurs when connected 
equipment exceeds the rating of battery-
powered outlets of the UPS.  Turn the UPS off, 
unplug at least one piece of equipment from 
battery-powered outlets, wait 10-seconds, 
reset the circuit breaker and turn the UPS on. 
On/Off On  Set  None 
 
Site Wiring Fault (MN 525 Only)-
 This indi-
cates a wiring problem with the AC wall outlet 
such as bad ground, missing ground, or re-
versed wiring.  Disconnect all electrical equip-
ment from the UPS’s outlets and have an 
electrician check the AC wall outlet to ensure 
proper wiring.