UPS 20-30 kVA, 230 V 0/60 Hz output  
User’s Guide
1026743 
Revision B
Battery information and settings:
ABM charging cycling disable
[Enabled], [Disabled]
Enabled
Charging temp compensation
[Enabled], [Disabled]
Enabled
Battery size setting
Step: 1 Watts/cell
24 Watts/cell
Number of 36 pcs. battery strings
0 (no batteries), 1, 2, 3, 4...
1 string
Battery low alarm level
Step: 0.01 V/cell
1.88 V/cell
Automatic battery support test
[Enabled], [Disabled]
Enabled
Maximum charging current
Step: 0.1 A [max. 25 Amps]
6 Amps
Output on, automatic delay time before turning 
the output on
[Disabled], [Set delay, step: 1 sec]
0 sec.
Output off, automatic delay time on battery 
after which output is turned off
[Disabled], [Set delay, step: 1 sec]
Disabled
User preferences:
Operation priority while rectifier input break
[On battery], [On bypass]
On battery
Site wiring fault w/ wrong Neutral connection [Enabled], [Disabled]
Enabled
Power Strategy
[Standard], [High Efficiency]
Standard
Parallel settings:
Parallel unit number
[Single unit], [Unit #1], [Unit #2], [Unit #3], 
[Unit #4]
Single unit
Parallel operation mode
[Redundant mode], [Capacity mode]
Redundant mode
Synchronization
[Enabled], [Disabled]
Enabled
Start auto calibration
Parallel XCP
[System], [Unit]
System
Minimum units to support load
[0], [1], [2], [3], [4]
2
Table 5 User setting in the LCD menu screen.