UPS OPERATING INSTRUCTIONS
EATON Powerware
®
 9395 UPS (1000–1100 kVA) Installation and Operation Manual  
S
  164201764 Rev 1 www.powerware.com
7−13
10. Press the 
CONTROLS
 pushbutton on the System Status menu bar. The UPM 1
Control Command screen is displayed.
11. On the UPM 1 Control Command screen, select 
UPM ON
.
12. Press the 
SELECT
 pushbutton on the UPM 1 Command menu bar.
13. Verify the following messages display sequentially on the UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM 1 rectifier and inverter turn on.
If the Inherent Redundancy option is enabled, a loss of redundancy alarm will be
issued. Silence the alarm and continue to Step 14.
UPM 2
 to start UPM 2.
15. Observe the following messages are displayed sequentially on the
UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM 2 rectifier and inverter turn on.
UPM 3
 to start UPM 3.
17. Verify the following messages display sequentially on the UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM 3 rectifier and inverter turn on. When the inverter reaches full voltage,
the UPS is ready to transfer to the Normal mode and supply the critical load.
UPM 4
 to start UPM 4.
19. Verify the following messages display sequentially on the UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM 4 rectifier and inverter turn on. When the inverter reaches full voltage,
the UPS is ready to transfer to the Normal mode and supply the critical load.
NOTE  To transfer to Normal mode after starting individual UPMs,