Examples of Instance 105/155 
 
Access the inverter parameter is enabled using byte 1 to 5 of this Instance. 
Set the communication number of the parameter to byte 2, 3 (Index), and the value to byte 4, 5 (Data). 
 
c Read the parameter cmod (Command mode selection, communication number is 0003). 
Instance 
Byte  15 14 13 12 11 10 9
8
7
6
5
4
3  2  1  0 
Hex. 
1,  0 
0
0
0
0 0 0 0
0
0
0
0x0000 
3,  2 
0
0
0
0 0 0 0
0
0
0
1 1 
0x0003 
Output Instance 105 
5,  4 
-
-
-
-
- -
-
-
-
-
1,  0 
0
0
0
0 0 0 0
0
0
0
0x0000 
3,  2 
0
0
0
0 0 0 0
0
0
0
1 1 
0x0003 
Input Instance 155 
(cmod is 0.) 
5,  4 
0
0
0
0 0 0 0
0
0
0
0x0000 
 
 
 
 
 
 
 
 
 
 
 
 
 
d Read the parameter f268 (Initial value of UP/DOWN frequency). 
Instance 
Byte  15 14 13 12 11 10 9
8
7
6
5
4
3  2  1  0 
Hex. 
1,  0 
0
0
0
0 0 0 0 0
0
0
0x0000 
3,  2 
0
0
0
0 0 1
1
0
0 0 0  0x0268 
Output Instance 105 
5,  4 
-
-
-
-
-
-
-
-
-
-
1,  0 
0
0
0
0 0 0 0 0
0
0
0x0000 
3,  2 
0
0
0
0 0 1
1
0
0 0 0  0x0268 
Input Instance 155 
(f268 is 60.0Hz.) 
5, 
4  0 0 0
1
0
1
1
1
1
1
1
0 0 0 0  0x1770 
 
 
 
 
 
 
 
 
 
 
 
 
 
3 Write “60 (Hz)” to the parameter sr1 (Preset speed 1, communication number is 0018). 
Instance 
Byte  15 14 13 12 11 10 9
8
7
6
5
4
3  2  1  0 
Hex. 
1, 0 
0
0
0
0 0 0 0 0
0
0
0x8000 
3, 2 
0  
0
0
0
0 0 0 0 0
0
1
0 0 0  0x0018 
Output Instance 105 
5, 
4  0 0 0
1
0
1
1
1
1
1
1
0 0 0 0  0x1770 
1,  0 
0
0
0
0 0 0 0 0
0
0
0x0000 
3,  2 
0
0
0
0 0 0 0 0
0
1
0 0 0  0x0018 
Input Instance 155   
(OK) 
5, 
4  0 0 0
1
0
1
1
1
1
1
1
0 0 0 0  0x1770 
1, 0 
0  1 
0
0
0
0 0 0 0 0
0
0
0x4000 
3,  2 
0
0
0
0 0 0 0 0
0
1
0 0 0  0x0018 
Input Instance 155   
(NG) 
(Error code *) 
5,  4 
0
0
0
0 0 0 0 0
0
0
0x0001 
 
*Data of "Error code" 
0x0001: Error