Connecting up 
 
4.4 Functional ground 
 
SCALANCE XB-200 
28
 
Operating Instructions, 02/2015, C79000-G8976-C359-01 
 
Note 
Pin assignment of the RJ-12 jack on the device 
The RJ-12 jack on the device has a pinout to match the RJ-11 plug of the connecting cable 
mentioned above. 
 
4.4 
Functional ground 
EMC disturbances are diverted to ground via the functional ground. This ensures the 
immunity of the data transmission. 
The functional ground must be implemented with low impedance. The connection of the 
functional ground must be established directly on the mounting plate or the DIN rail terminal. 
The SCALANCE XB-200 has a terminal for functional ground, refer to the section "Power 
supply (Page 25)". Keep to the specified cross-sectional area for the functional ground. 
The terminal is identified by the following symbol for the functional ground 
.  
Follow the steps below to connect the functional ground: 
1.  Connect the terminal of the SCALANCE XB-200 with as short a cable as possible ≤ 150 
mm and with the required cross-sectional area to a grounded part of the system (DIN 
rail). 
2.  Connect the DIN rail with the ground of the system. 
Protective/functional ground 
 The connection of the reference potential surface with the protective ground system is 
normally in the cabinet close to the power feed-in. This ground conducts fault currents to 
ground safely and according DIN/VDE 0100 is a protective ground to protect people, animals 
and property from too high contact voltages.  
Apart from the protective ground, there is functional grounding in the cabinet. According to 
EN60204-1 (DIN/VDE 0113 T1) electrical circuits must be grounded. The chassis (0 V) is 
grounded at one defined point. Here, once again the grounding is implemented with the 
lowest leakage resistance to ground in the vicinity of the power feed-in. 
With automation components, functional ground also ensures interference-free operation of 
a controller. Via the functional ground, interference currents coupled in via the connecting 
cables are discharged to ground.