Appendix A:  Trip Curves & Equations
Siemens Energy & Automation, Inc.
 
 55
Figure A.7 Extremely Inverse Curve (SEA6)
Figure A.8 Slightly Inverse Curve (SEA7)
0.01
0.1
1
10
100
1000
1
10
50
9.9
7.0
5.0
3.0
1.5
0.5
0.1
Multiples of Pickup
T
ime to T
rip (Seconds)
T
ime Dial
0.01
0.1
1
10
100
1
10
50
9.9
7.0
5.0
3.0
1.5
0.5
0.1
Multiples of Pickup
T
ime to T
rip (Seconds)
T
ime Dial
A.3 Definite Inverse Equation
Equation A.2 The ISGS provides an emulation of the 
popular CO-6 Definite Inverse characteristic. This curve is 
defined by the equations shown in Equation A.3.
Equation A.3 Definite Inverse Equation
In Equation A.3, the time dial term 6.33D + 0.37 is neces-
sary to convert the time dial range defined by Westinghouse
and the range that Siemens is using.
Equation (1) is valid for values of I/Ip greater than 1.5 and
equation (2) is valid for values of I/Ip between 1.0 and 1.5
(note that the equation is undefined at I/Ip = 1.0).
Trip Characteristic
Reset Characteristic
T = time to trip, in seconds
 = multiple of pickup setting
D = time dial setting, 0.1 to 9.9 in steps of 0.1
tr = reset constant = 1.0394
N = inverse constant = 2.54096
For
i
ip
-----
1.5
T
785
671
i
ip
----
N
1.19
-------------------------------
+
6.33D 0.37
+
24000
-------------------------------
×
=
>
For1.0
i
ip
-----
1.5:   
T
785
671
i
ip
----
N
1.19
-------------------------------
+
6.33D 0.37
+
24000
----------------------------------
×
=
<
<
For
i
ip
-----
1:   
T
t
r
D
i
ip
----
N
1
------------------------
=
<
i
ip
-----
 
 
 
A