Appendix D:  Acceptance Test Procedures
76
 
Siemens Energy & Automation, Inc.
ISGS Acceptance Test 
Directional Neutral Time Overcurrent (67N)
Function
(Only Available with Phase-Neutral Connected VTs)
Set the ISGS as follows:
Parameter Set A
7103
5000:5 Current Transformer (CT)
1102
Curve SEA 5, Very Inverse
2002
1 A Nominal Pickup
2003
Time Dial per Chart
2005
Impedance to 45°
1907
Direction to Reverse
1908
Trip Matrixed to Trip 1 Contact
6401
Enable 67
2001
Disable Other Conflicting Functions
1501, 1551, 1601, 1651, 1801, 1901, 2001, 2301
Raise 51 Pickup to Maximum
1703
Phase
N
Connections
1. Connect the appropriate source of control voltage to terminals 13 (+) and 12 (-).
2. Relay Disabled contact on terminals 19 and 20 opens.
3. Connect suitable variable source current
to phase A, terminal 3,
to phase B, terminal 5,
to phase C, terminal 7,
Connect terminals 4, 6, and 8 to terminal 9.
Connect terminal 10 to the common of the current sources.
4. Connect suitable AC voltage
to phase A, terminals 41 and 42,
to phase B, terminals 43 and 44,
to phase C, terminals 45 and 46,
Connect timer to Trip 1 contacts, terminals 1 and 2.
Pickup
5. Apply nominal voltage to the relay’s voltage inputs, for example,
for example,  69 V 
 0 to phase A, 
69 V 
 240 to phase B, 
69 V 
 120 to phase C.
Apply 2x pickup current to phase A in forward direction, for example,
for example,  2.0 A 
 0 to phase A, 
2.0 A 
 240 to phase B, 
2.0 A 
120 to phase C.
-relay should not go into pickup,
-reset test current to zero A,
D