Siemens SCALANCE X-200 사용자 설명서

다운로드
페이지 296
Configuration / diagnostics using remote mechanisms 
 
6.3 Configuration using Web Based Management (WBM) and Command Line Interface (CLI) 
 
SCALANCE X-200 
184
 
Operating Instructions, 12/2011, A5E00349864-19 
Ring Redundancy Manager 
 Here you can choose whether the "active" status of the redundancy manager triggers an 
error. 
Standby Manager (only SCALANCE X200IRT) 
Here, you can choose whether the "master" status and "passive" or "slave" and "active" or 
partner not found triggers an error. 
Enable Link Down Monitoring 
Error message when the status of the port is "Link down". Here, you can enable/disable 
monitoring of the link status for the individual ports. 
Enable Link Up Monitoring 
Error message when the status of the port is "Link up". Here, you can enable/disable 
monitoring of the link status for the individual ports. 
 
 
Note 
With the default setting as supplied, no port is monitored; in other words, the fault mask is 
empty. 
As default, the power supply is also not monitored. 
 
Syntax of the Command Line Interface 
Table 6- 11  Fault Mask - CLI\X200> 
Command 
Description 
Comment 
info 
Displays information on the "X-200" menu item. 
 
fault  
Displays the fault status. 
 
downmask <1-n> <E¦D>  Specifies a port mask for the ports for which the 
monitoring of a link down event is enabled. 
Administrator only. 
upmask <1-n> <E¦D> 
Specifies a port mask for the ports for which the 
monitoring of a link up event is enabled. 
Administrator only. 
others <P> <E¦D> 
 Specifies the fault mask for: 
P - power mask 
Administrator only.