Network topologies / media redundancy 
 
2.4 MRP 
 
SCALANCE X-200 
26
 
Operating Instructions, 12/2011, A5E00349864-19 
Topology 
The following schematic shows a possible topology for devices in a ring with MRP. 
10
9
8
7
6
5
4
3
2
1
5HGXQGDQF\GRPDLQ
+0,VWDWLRQ
(QJLQHHULQJVWDWLRQ
(76
(70
(7SUR
6ZLWK&3$GYDQFHG
6&$/$1&(;VZLWFK
3&ZLWK&3
6ZLWK&3$GYDQFHG
 
Figure 2-9 
Example of a ring topology with the MRP media redundancy protocol 
The following rules apply to a ring topology with media redundancy using MRP:   
●  All the devices connected within the ring topology are members of the same redundancy 
domain. 
●  One device in the ring is acting as redundancy manager. 
●  All other devices in the ring are redundancy clients. 
Non MRP-compliant devices can be connected to the ring via a SCALANCE X switch or via 
a PC with a CP 1616. 
 