Installation 
••••  17 
Wall or Rack Mounting Installation 
The Advance DataNET Hub should be: 
•  Installed in a location that is free from shock and vibration. 
•  Protected from direct sunlight and extremes of temperature. 
•  It is recommended that the DNH be mounted within a shelter. This 
prevents DNH from being exposed to outside environmental condi-
tions. 
 
The unit is designed for standard wall or Zone 1 wall installations, or 19-
inch rack installations; see Chapter 1. Figures 1-5, 1-6 and 1-7. Shown 
below is a typical wall mount installation for NEC Division 2 or non-rated 
areas. The photo shows the unit wall mounted in an analyzer house. 
Note that the AC Power (Mains) breaker is located in close proximity of 
the unit. Also note the I/O connections to the DNH. 
POWER & DNH
CABLE OR WIRING
 CONNECTIONS
AC BREAKER
 PROTECTION
 
 
The mounting wall must be capable of supporting the weight of the unit; 
see Chapter 1., Specifications and Figures 1-6 and 1-7. 
Wall Mount Installation: Use four, 5/16-inch (M8) or 3/8-inch (M10) lag 
bolts to mount the unit to the wall. Mounting bolts must be secured to 
solid wall construction members such as studs and into the wall only. 
Allow adequate clearance on the left side to allow the door to swing 
open. 
Zone 1 Wall Mount Installation: Use four, ¾-inch (M20) lag bolts to 
mount the NAU to the wall. Mounting bolts must be secured to solid wall 
construction members such as studs and into the wall only. 
 
Instructions 
Package 
Configurations 
Wall Mounting