Siemens DataNET Hub (DNH) 사용자 설명서

다운로드
페이지 97
24  
••••  Installation 
2000585-001 
CE Installations, 
Continued
 
 
3.  A split ferrite filter must be clamped to DataNET copper wire and 
fixed immediately to the outside of the DNH; use Siemens Applied 
Automation part number 1173000-013 ferrite contained in the CE In-
stallation Kit. This is required to meet the Conducted Immunity re-
quirement for CE/EMC Heavy Industrial. All other CE/EMC Heavy 
Industrial requirements are met without the use of a ferrite clamp. 
4.  Shielded Ethernet cable must be used for all Ethernet connections, 
in and outside the GC, and coupled through the enclosure using a 
shielded RJ-45 coupler; use Siemens Applied Automation part num-
ber 1183200-003 contained in the CE Installation Kit. A mounting 
plate (Siemens Applied Automation part number 2020261-001) is 
also available to accomplish this. If needed for Zone 1 installation, 
Siemens Applied Automation part numbers 2017984-001 and 
2017985-001 are available to maintain purge. If a PG gland is used 
to make the 360-degree termination of the Ethernet shield at the en-
closure, the Installation Kit and other parts are not required.