Installation and Commissioning 
 
Operating Instructions for SCALANCE X-400 Industrial Ethernet Switches 
102 
C79000-G8976-C186-03 
 
Notice 
Changing the switch settings during operation causes fault displays and activates 
the signaling contact. The settings are adopted only after the device is restarted. 
The RM switch allows you to configure the SCALANCE X414-3E as a redundancy 
manager in a ring with redundancy manager. 
The STBY switch is reserved for future functionality and does not currently have 
any function. 
With switches R1 and R2, you can specify either the two ports in slot 5, the two 
ports in slot 6 or the first ports of slots 6 and 7 as ring ports. If you do not want any 
ring ports defined, both switches must be set to ON
Switch Status 
Meaning 
RM 
OFF 
SCALANCE X414-3E is not a redundancy manager. 
 
ON 
SCALANCE X414-3E is a redundancy manager. 
STBY OFF 
 ON 
No function, reserved for future applications. 
R1 OFF 
R2 OFF 
Ports in slot 5 (gigabit ports) are ring ports. 
R1 ON 
R2 OFF 
Ports 1 and 2 of slot 6 are ring ports. 
R1 OFF 
R2 ON 
Port 1 of slot 6 is first ring port. 
Port 1 of slot 7 is second ring port. 
R1 ON 
R2 ON 
No ring redundancy. 
When shipped, the factory settings apply (see section 6.5).