GAS SPILLAGE SENSING KIT  
Model:  GSK-3, GSK-4, GSK-250M 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Installation of a spillage SAFETY Switch is recommended for LP and Natural gas fired systems with draft 
hoods, draft diverter, or gas barometric draft controls. This device is installed to detect flue gas spillage 
caused by a blocked flue system and/or inadequate draft. This device MUST be installed by a qualified 
installer in accordance with the manufacturer's installation instructions. Wiring MUST be in accordance 
with the National Electrical Code and applicable local codes. 
Before and after adding this safety control on existing appliances, an installation inspection in accordance 
with the National Fuel Gas Code 54, Z223.1 Appendix H should be performed and a combustion analysis 
is recommended to determine the operating condition of the appliance. 
CAUTION: Disconnect Electrical Power When Wiring Spillage Switch 
 
LOAD RATING 
MODEL 
P/N 
CONTACT 
MATERIAL 
AMPS
VOLTS 
SETPOINT °F 
RESET 
SWITCH 
TYPE 
APPLICATION 
GSK-3 
46086400 
GOLD 
24VA 
mV-24AC 
180 
MANUAL 
SPST NC 
Gas-fired mV or 24VAC 
GSK-4 
46086402 
GOLD 
24VA 
mV-24AC 
200 
MANUAL 
SPST NC 
Gas-fired mV or 24VAC, 
where slower response 
time is a requirement 
GSK-250M 
46086404 
SILVER 
24VA 
mV-24AC 
250 
MANUAL 
SPST NC 
Steam Boilers