Instruction Manual
45
status of a UPS, writing it to a file. 
 
All these clients all run on the ECS0016 (for Management Console 
presentations) but they also are run remotely (on locally powered 
servers and remote monitoring systems).
This layered NUT architecture enables: 
Multiple manufacturer support: 
 NUT can monitor USB models from  
79 different manufacturers with a unified interface
Multiple architecture support: 
NUT can manage serial and USB 
connected models with the same common interface. SNMP equipment 
can also be monitored (although at this stage this is still pre-release 
with experimental drivers and this feature will be added to the 
ECS0016’s embedded UPS tools in future release). 
Multiple clients monitoring the one UPS:
 Multiple systems may 
monitor a single UPS using only their network connections and there’s 
a wide selection of client programs) which support monitoring UPS 
hardware via NUT (Big Sister, Cacti, Nagios, Windows and more. Refer 
www.networkupstools.org/client-projects.)
So NUT supports the more complex power architectures found in data 
centers, computer rooms and NOCs where many UPSes from many 
vendors power many systems with many clients and each of the larger 
UPSes power multiple devices and many of these devices are themselves 
dual powered. 
Environmental Monitoring
The Environmental Monitor Device (EMD) connects to any ECS0016 
serial port and each console server can support multiple EMDs. Each 
EMD device has one temperature and one humidity sensor and two 
general purpose status sensors which can be connected to a smoke 
detector, water detector, vibration or open-door sensor.