Installation Drawings
39
Figure 26 Control wiring for comms board
EXTERNAL MODEM
SEE DETAIL A
“NO CUSTOMER 
CONNECTION”
PS213003
Rev. 02
LIEBERT
SITESCAN
SEE DETAIL B
“NO CUSTOMER 
CONNECTION”
J81
J1A
COMMS BOARD
02-810015-XX
TB55
TB56
TB51
SEE NOTE 2
CUSTOMER-SUPPLIED
INTERCONNECTING CABLE
TO EXTERNAL MODEM
CUSTOMER-SUPPLIED
INTERCONNECTING CABLE
TO LIEBERT SITESCAN
SEE NOTES 1 & 2
DETAIL A
9
1 2 3 4 5 6 7 8
J81
RI
DS
R
RX TX DT
R
GN
D
DC
D
RT
S
CT
S
DETAIL B
TB 55
1 2 3
NOTES
1. Maximum cable length 1000 feet (300 meters) with 
twisted pair cable #22 AWG 300V minimum.
2. Signal voltage 5VDC, current 10mA.
3. Refer to installation, operation and maintenance 
manual for configuring the COMMS board.
4. All control wiring (by others) must be run separate from 
power wiring. Control wiring runs should not be 
combined in the same conduit.
5. Refer to control connection location diagram (Figure 21 
6. All wiring must be in accordance with national and 
local electrical codes.