Liebert 3000VA 사용자 설명서

다운로드
페이지 44
Operation and Display Panel
17
Liebert
®
 GXT3
3.0
O
PERATION
 
AND
 D
ISPLAY
 P
ANEL
The operation and display panel, shown in Figure 17, is on the front panel of the Liebert GXT3 (see 
Figure 17 Operation and display panel
3.1
Control Buttons
The operation and display panel has two control buttons: the On/Alarm Silence/Manual Battery Test 
button and the Standby/Manual Bypass button.
3.1.1 On/Alarm Silence/Manual Battery Test button
The On/Alarm Silence/Manual Battery Test button controls output power to connected load(s) and 
has three functions (see Table 3).
3.1.2 Standby/Manual Bypass button
The Standby/Manual Bypass button controls output power to connected load(s) and has two functions 
Table 3
Functions of the On/Alarm Silence/Manual Battery Test button
Function
Operation
Description
ON
Press the button once for 3 seconds
To start up the UPS
Alarm silence
Press the button for at least half a second
To silence alarms
Manual Battery Test
Press the button for at least half a second while 
operating in Mains (AC) Mode with no alarms present.
To initiate a manual battery test
1. The low battery and bypass reminder alarms cannot be silenced.
2. After the alarm is silenced, UPS will reactivate the alarm system to alert of additional problems.
Table 4
Functions of the Standby/Manual Bypass button
Function
Operation
Description
Manual Bypass
Press the button once and hold it for about
To initiate a manual transfer of the connected
loads to the internal bypass, if available
Standby
Press the button twice within four seconds while
the UPS is in Manual Bypass or Battery Mode.
To shut down the UPS and shut Off all power
to the connected loads
1. If the bypass is not available due to voltage or frequency, pressing this button once will be ignored.
2. Perform all necessary shutdown procedures on connected loads before turning Off the Liebert GXT3.
Liebert
®
GXT3
AC Power System
3000VA
Battery Level Indicators
Load Level Indicators
Bypass Indicator
Inverter Indicator
Battery Indicator
Standby/Manual Bypass Button
On/Alarm Silence/Manual 
Battery Test Button
AC Input Indicator
Fault Indicator