Liebert 3000VA 사용자 설명서

다운로드
페이지 44
Specifications
33
Liebert
®
 GXT3
9.0
S
PECIFICATIONS
The specifications of the Liebert GXT3 are listed in Table 11 and Table 12.
Table 11
Specifications of GXT3-700RT230 and GXT3-1000RT230 UPS
Parameters
Product model
GXT3-700RT230
GXT3-1000RT230
Model Rating
700VA/630W
1000VA/900W
Dimensions, D x W x H, mm (in)
Unit
497 x 430 x 85 (19.6 x 16.9 x 3.3)
Shipping
617 x 570 x 262 (24.3 x 22.4 x 10.3)
Weight, kg (lb)
Unit
16.8 (37)
Shipping
20 (44)
Input AC
Voltage Range (typical)
230VAC nominal; variable based on output load
90% ~ 100% loading
177VAC/280VAC
70% ~ 90% loading
168VAC/280VAC
30% ~ 70% loading
150VAC/280VAC
0 ~ 30% loading
115VAC/280VAC
Frequency
40Hz ~ 70Hz; Auto Sensing
Input Power Receptacle
C14
Output AC
AC-AC Efficiency
> 88% AC-AC, minimum
Output Receptacles
C13 × 6
Voltage
220/230/240VAC (user configurable); ±3%
Frequency
50Hz or 60Hz
Waveform
Sine wave
Mains (AC) Mode Overload
200% for 2 seconds; 150% for 1 minute with transfer to bypass
Internal Battery Charger
Charger Current
1.3
Battery
Type
Valve-regulated, nonspillable, lead acid
Qty × V× Rating
4 × 12V × 5.0Ah
Battery Mfr/Part#
YUASA/NPH5-12; CSB/ HR 1221W; CSB/GP1245
Backup Time
See Table 15 - Battery run times
Recharge Time
3 hours to 90% capacity after full discharge with 100% load till UPS
auto-shutdown (Internal Batteries Only)
Environmental Requirements
Operating Temp
Storage Temp
-15ºC to +50ºC (5ºF to 122ºF)
Relative Humidity
0%RH to 95%RH, non-condensing
Operating Elevation
Up to 3000m (10,000 ft.) at 25ºC (77ºF) without derating
Storage Elevation
15,240 (50,000 ft.) maximum
Audible Noise
< 46 dBA, at 1 meter (3.2ft) from the rear
< 43 dBA, at 1 meter (3.2ft) from the front or sides
Agency
Safety
IEC/EN/AS 62040-1:2008, GS mark
RFI/EMI
IEC/EN/AS 62040-2 2nd Ed (Category C2) = CISPR22 Class A
Surge Immunity
IEC/EN 62040-2 2nd Ed (IEC/EN 61000-4-5)
Transportation
ISTA Procedure 1A