Table 2B Direct Vent Minimum / Maximum Allowable Air / Vent Lengths
Table 2C Room Air Minimum / Maximum Allowable Air / Vent Lengths
Model 
AIR INLET
VENT
Input 
De-Rate per   
25 feet of Vent
Air Intake 
Diameter
Air Intake
Min. Length
Air Intake
Max. Length
Vent
Diameter
Vent
Min. Length
Vent 
Max. Length
FB 0751
6"
12'
100'
6"
18'
100'
0%
FB 1001
6"
12'
100'
6"
18'
100'
0%
FB 1251
6"
12'
100'
8"
18'
100'
0%
FB 1501
8"
12'
100'
8"
18'
100'
0%
FB 1751
8"
12'
100'
8"
18'
100'
0%
FB 2001
8"
12'
100'
8"
18'
100'
0%
Model 
Vent
Diameter
Vent
Min. Length
Vent 
Max. Length
Input De-Rate per    
25 feet of Vent
FB 0751
6"
18'
100'
0%
FB 1001
6"
18'
100'
0%
FB 1251
8"
18'
100'
0%
FB 1501
8"
18'
100'
0%
FB 1751
8"
18'
100'
0%
FB 2001
8"
18'
100'
0%
17
        
Installation & Operation Manual
2  
General
 
venting 
Table 2A-2 Approved Stainless Steel Terminations and Adapters - Category IV
Model
ProTech
Z Flex
Heat Fab
Adapter
Intake
Adapter
Intake
Adapter
Flue
Intake
751-1001
810003974
810003269
2SVDSA06
2SVEE0690
9601MAD
CCK06TM
9690
9692
1251
810003980
810003281
2SVDSA06
2SVEE0690
9801MAD
CCK08TM
9690
9692
1501-2001
810003980
810003357
810003369
2SVDSA08
2SVEE0890
9801MAD
CCK08TM
9890
9892
Model
Metal-Fab
Security Chimney
ICC
Adapter
Flue
Intake
Adapter
Flue
Intake
Adapter
Flue
Intake
751-1001
6FCGPVCA
MC
6-36"
6FCGSW90L SS6PVCU
SS0MCU
4" - 24"
SS6ST90AU
SSD0STAUK
4" - 24"
HE-6DSA-F
HE-6MC-F
HE-6RC-F
HE-6E90-F
HE-6SCR-F
1251
8FCGLCA
MC
6-36"
6FCGSW90L SS8CRESTU
SS0MCU
4" - 24"
SS6ST90AU
SSD0STAUK
4" - 24"
HE-8DSA-F
HE-8SCR-F
HE-8MC-F
HE-6E90-F
HE-6SCR-F
1501-2001
8FCGLCA
MC
6-36"
8FCGSW90 SS8CRESTU
SS0MCU
4" - 24"
SSE8E9OU
SD0STAUK
4" - 24"
HE-8DSA-F
HE-8SCR-F
HE-8MC-F
HE-8E90-F
HE-8SCR-F
Model
Jeremias
Adapter
Flue
Intake
751-1001
SWKL6-KLC SWKL6-WRC SWKL6-90ET
1251
SWKL8-KLC SWKL8-WRC SWKL6-90ET
1501-2001
SWKL8-KLC SWKL8-WRC SWKL8-90ET