Lochinvar 751 - 2001 사용자 설명서

다운로드
페이지 68
        
Installation & Operation Manual
 
21
2  
General
 
venting   
Model
Manufacturer Vent Model
Vent Type
Adapter Number
Joint Connector
Sidewall Kit*
Retaining Bracket / 
Adapter*
751-1001
Centrotherm
Eco Systems 
Innoflue
Single-Wall 
Flex
ISAAL0606
--
--
IATP0606 / 
ISTAGL0606
DuraVent
(M & G)
PolyPro
Single-Wall 
Flex
FSA-6PVCM-
6PPS
--
6PPS-HLK
--
1251-2001
Centrotherm
Eco Systems 
Innoflue
Single-Wall
ISAA0808
--
--
--
DuraVent
(M & G)
PolyPro
Single-Wall
FSA-AU8-8PP
--
8PPS-HSTL
--
 * These parts are only needed if the sidewall termination assembly is used (see FIG. 4-1C on page 25).
Polypropylene 
This product has been approved for use with polypropylene 
vent with the manufacturers listed in Table 2F.
All terminations must comply with listed options in this 
manual and be a single-wall vent offering.  
For support and special connections required, see the 
manufacturer's instructions.  All vent is to conform to standard 
diameter and equivalent length requirements established.
When determining equivalent combustion air and vent length 
for polypropylene single-wall piping contact the manufacturer.    
Use only the adapters and vent system  listed 
in Tables 2F and 2G.  DO NOT mix vent 
systems of different types or manufacturers.  
Failure to comply could result in severe 
personal injury, death, or substantial 
property damage.
 WARNING
Installations must comply with applicable 
national, state, and local codes.  For 
Canadian installation, polypropylene vent 
must be listed as a ULC-S636 approved 
system.  
Installation of a polypropylene vent system 
should adhere to the vent manufacturer’s 
installation instructions supplied with the 
vent system.
Table 2F Polypropylene Vent Pipe and Fittings
 WARNING
Insulation should not be used on 
polypropylene venting materials.  The use 
of insulation will cause increased vent wall 
temperatures, which could result in vent pipe 
failure.
The installer must use a specific vent starter 
adapter at the flue collar connection. The 
adapter is supplied by the vent manufacturer 
to adapt to its vent system.  See Table 2F 
for approved vent adapters.  Discard CPVC 
starter piece.
 NOTICE
All vent connections MUST be secured by 
the vent manufacturer's joint connector 
(FIG. 2-4).
 NOTICE
Figure 2-4 Near Boiler Polypropylene Venting 
IMG01149
8" POLYPROPYLENE
PIPE (FIELD SUPPLIED)
8" POLYPROPYLENE 
ADAPTER (FIELD 
SUPPLIED)
MODELS 1251 - 2001
IMG01148
6" POLYPROPYLENE 
PIPE (FIELD SUPPLIED)
6" POLYPROPYLENE 
ADAPTER (FIELD
SUPPLIED)
MODELS 751 - 1001
 NOTICE
 NOTICE
Table 2G Approved Polypropylene Terminations
Approved Polypropylene Vent Manufacturers
Make
Model
Centrotherm Eco Systems
InnoFlue SW/Flex
Duravent (M & G Group)
PolyPro Single-Wall / PolyPro Flex
Factory installed vent connections are sized 
for stainless steel venting.
 NOTICE