Installation & Operation Manual
4  
Sidewall direct venting 
Vent/air termination – sidewall 
 
TO BOILER
INTAKE AIR
CONNECTION
FROM BOILER
VENT PIPE
CONNECTION
VENT / AIR
TERMINATION
GRADE OR
SNOW LINE
12"
MIN
12"
MIN
TO
OVER-
HANG
POSSIBLE ORIENTATIONS
Figure 4-1C PVC/CPVC/Polypropylene Sidewall 
Termination of Air and Vent
Do not exceed the maximum lengths of the 
outside vent piping shown in FIG. 4-1C. 
 
Excessive length exposed to the outside could 
cause freezing of condensate in the vent pipe, 
resulting in potential boiler shutdown.
 WARNING
3.  The air piping must terminate in a down-turned elbow 
as shown in FIG. 4-1B.  This arrangement avoids 
recirculation  of flue products into the combustion air 
stream.
4.  The vent piping must terminate in an elbow pointed 
outward or away from the air inlet, as shown in FIG. 4-1B.
36” (914 MM) MIN
48” (1219 MM) MAX
12” (305 MM)
MIN
Figure 4-1B PVC/CPVC/ Polypropylene Sidewall 
Termination of Air and Vent w/Field Supplied Fittings
Model
Kit #
Air
Vent
Centerline 
Width
751 - 1001 100157612 6" (152 mm) 6" (152 mm) 7 3/4" (197 mm)
Table 4A Sidewall Vent Kits
TO BOILER INTAKE
AIR CONNECTION
FROM BOILER VENT
PIPE CONNECTION
36" (914 MM) MIN
48" (1219 MM) MAX
12" (305 MM) MIN
GRADE OR
SNOW LINE
Figure 4-2B Stainless Steel Sidewall Termination  w/Field 
Supplied Fittings
36" (914 MM) MIN 
48" (1219 MM) MAX 
12" (305 MM) MIN
FROM BOILER
VENT PIPE
CONNECTION
TO BOILER
INTAKE AIR
CONNECTION
BIRD SCREEN
BIRD SCREEN
GRADE OR
SNOW LINE
Figure 4-2A PVC/CPVC/ Polypropylene Sidewall 
Termination w/Field Supplied Fittings
PVC/CPVC or ABS is acceptable air inlet pipe material.
 
 
NOTICE
5.  Maintain clearances as shown in FIG.’s 4-1A thru 4-4, 
 
pages 24 thru 26.  Also maintain the following:
a. Vent 
must 
terminate:
 
• At least 6 feet (1.8 m) from adjacent walls.
 
• No closer than 12 inches (305 mm) below roof 
  
overhang.
 
• At least 7 feet (2.1 m) above any public walkway.
 
• At least 3 feet (.9 m) above any forced air intake 
 
  within 10 feet (3 m).
 
• 
No closer than 4 feet (1.2 m) below or 
 
  horizontally from any door or window or any other 
 
  gravity air inlet.
b.  Air inlet must terminate at least 12 inches (305 mm) 
 
above grade or snow line; at least 3 feet (.9 m) 
 
below the vent termination (FIG. 4-1B); and the vent 
 
pipe must not extend more than 24 inches (610 mm) 
 
vertically outside the building.
c.  Do not terminate closer than 4 feet (1.2 m) 
 
horizontally from any electric meter, gas meter, 
 
regulator, relief valve, or other equipment.  Never 
 
terminate above or below any of these within 4 feet  
 
(1.2 m) horizontally.