Installation & Operation Manual
 WARNING
Do not check for gas leaks with an open 
flame -- use the bubble test.  Failure to 
use the bubble test or check for gas leaks 
can cause severe personal injury, death, or 
substantial property damage.
14.  Turn on the gas supply at the manual gas valve.
15.  Turn the power switch to the “ON” position.
16.  Adjust the temperature set point on the control panel of 
 
the SMART TOUCH control module to the desired 
 
water temperature so the appliance will call for heat.
17.  Check burner performance by cycling the system while 
 
you observe burner response.  The burner should ignite 
 
promptly.  Flame pattern should be stable.  Turn system 
 
off and allow burner to cool, then cycle burner again to 
 
ensure proper ignition and flame characteristics.
Gas valve replacement
The gas valve MUST NOT be replaced with a 
conventional gas valve under any circumstances.  As 
an additional safety feature, the  gas valves have flanged 
connections to the venturi and the blower.
Figure 6-4 Inlet Gas Supply Check 
DO NOT adjust or attempt to 
measure gas valve outlet pressure. 
 
Attempting to alter or measure 
the gas valve outlet pressure could 
result in damage to the valve, 
causing potential severe personal 
injury, death, or substantial property 
damage.
Failure to follow all precautions 
could result in fire, explosion, or 
death!
 WARNING
 WARNING
6  
Gas connections 
(continued)