Lochinvar 751 - 2001 사용자 설명서

다운로드
페이지 68
        
Installation & Operation Manual
8
1  
Determine boiler location
Provide air openings to room:
The Crest alone in boiler room
1.  No air ventilation openings into the boiler room are 
needed when clearances around the Crest are at least 
equal to the SERVICE clearances shown in FIG. 1-1.  
For spaces that do NOT supply this clearance, provide 
two openings as shown in FIG. 1-1.  Each opening must 
provide one square inch free area per 1,000 Btu/hr of 
boiler input.
2.  Combustion air openings are required when using the 
Room Air Option on page 27 of this manual.
The Crest in same space with other gas or oil-fired 
appliances
1.  Follow the National Fuel Gas Code (U.S.) or CSA B149.1 
(Canada) to size/verify size of the combustion/ventilation 
air openings into the space.
The space must be provided with 
combustion/ventilation air openings 
correctly sized for all other appliances 
located in the same space as the Crest.
Failure to comply with the above warnings 
could result in severe personal injury, 
death, or substantial property damage.
2.  Size openings only on the basis of the other appliances in 
the space.  No additional air opening free area is needed 
for the Crest when it takes its combustion air from 
outside (direct vent installation).
Do not install the boiler on carpeting even if 
foundation is used.  Fire can result, causing 
severe personal injury, death, or substantial 
property damage.
If flooding is possible, elevate the boiler sufficiently to prevent 
water from reaching the boiler.
Flooring and foundation
Flooring
The Crest is approved for installation on combustible flooring, 
but must never be installed on carpeting.
Vent and air piping
The Crest requires a special gas vent system, designed for 
pressurized venting.  
The boiler is to be used for either direct vent installation or 
for installation using indoor combustion air.  When room air 
is considered, see page 27 of this manual.  Note prevention of 
combustion air contamination below when considering vent/
air termination.
Vent and air must terminate near one another and may be 
vented vertically through the roof or out a side wall, unless 
otherwise specified.  You may use any of the vent/air piping 
methods covered in this manual.  Do not attempt to install 
the Crest using any other means.
Be sure to locate the boiler such that the vent and air piping 
can be routed through the building and properly terminated.  
The vent/air piping lengths, routing and termination method 
must all comply with the methods and limits given in this 
manual.
Prevent combustion air contamination
Install air inlet piping for the Crest as described in this 
manual.  Do not terminate vent/air in locations that can 
allow contamination of combustion air.  Refer to Table 1A, 
page 9 for products and areas which may cause contaminated 
combustion air.
Ensure that the combustion air will not 
contain any of the contaminants in Table 
1A, page 9.  Contaminated combustion 
air will damage the boiler, resulting in 
possible severe personal injury, death 
or substantial property damage. Do not 
pipe combustion air near a swimming 
pool, for example.  Also, avoid areas 
subject to exhaust fumes from laundry 
facilities. These areas will always contain 
contaminants.
 WARNING
 WARNING
 WARNING
 
Assure that the floor and structure is 
sufficient to support the installed weight 
of the boiler, including the water content 
in the heat exchanger.  If not, structural 
building failure will result, causing severe 
personal injury, death, or substantial 
property damage.
 WARNING
Recommended clearances for service access
 -   Sides ..............................................................................  24" 
-   Rear ...............................................................................  24"
 -   Front .............................................................................  30"
 -   Top ................................................................................  24"
If you do not provide the recommended 
service clearances shown, it may not be 
possible to service the boiler without 
removing it from the space.
 NOTICE
Maintain minimum specified clearances for adequate 
operation.  All installations must allow sufficient space for 
servicing the vent connections, water pipe connections, piping 
and other auxiliary equipment, as well as the appliance.  The 
clearance labels on each appliance note the same service and 
combustible clearance requirements as shown in this manual. 
Multiple boilers may be installed side by side with no clearance 
between adjacent boilers because this boiler is approved for 
zero clearance from combustible surfaces; however, service 
access will be limited from the sides.
Consult the Venting section of this manual for specific 
installation instructions for the appropriate type of venting 
system that you will be using.