7SA511 Line Protection Relay
Reference A
July 27, 1995
A-19
Table A-7. Selected Measurement Quantities in Grounded Systems, with
Impedance Fault Detection
Fault Detection
Phase Loops
Selected Loop
Selected Setting Parameter
L1-E
L2-E
L3-E
L1-E
L2-E
L3-E
irrelevant
L1-L2
L2-L3
L3-L1
L1-L2
L2-L3
L3-L1
irrelevant
L1-E, L2-E
L2-E, L3-E
L1-E,
L3-E
L1-L2
L2-L3
L3-L1
2PH-E FLTS =
PHASE-PHASE
L1-E, L2-E
L2-E, L3-E
L1-E,
L3-E
L1-E
L2-E
L3-E
2PH-E FLTS =
LEADING PH-E
L1-E, L2-E
L2-E, L3-E
L1-E,
L3-E
L2-E
L3-E
L1-E
2PH-E FLTS =
LAGGING PH-E
L1-L2, L2-L3
L2-L3,
L3-L1
L3-L1,
L1-L2
L1-L2
L2-L3
L3-L1
irrelevant
L1-E, L2-E, L3-E
L1-L2, L2-L3, L3-L1
L3-E
L3-L1
3PH FAULTS =
E/F CONTROL
L1-E, L2-E, L3-E
L1-L2, L2-L3, L3-L1
L3-L1
L3-L1
3PH FAULTS =
PH-PH ONLY
L1-E, L2-E, L3-E
L1-L2, L2-L3, L3-L1
L3-E
L3-E
3PH FAULTS =
PH-E ONLY
A.3.3  Fault Loop Determination in Ungrounded Systems (Optional)
In isolated or compensated networks, currents resembling a short circuit are not present in the
case of a single-phase ground fault. Only a displacement of the voltage triangle occurs, as
illustrated in Figure A-7, and this condition does not represent any immediate danger to network
operation. In this case, the distance protection must not trip since the phase-to-ground voltage of
the faulty phase is zero throughout the network. A trip would lead to, at each measuring point, a
measured impedance equal to zero for the faulty phase-to-ground loop. Therefore, pickup of one
single phase-to-ground fault detector is avoided in the 7SA511 relay.