Wiring Diagram –
Single Door Freezer
PLUG-IN-CORD
WHITE
WHITE
EVAP
FAN
COND
FAN
DEFROST
TEMP. LIMIT
SWITCH
OPEN
@ 40
°
F
CLOSE
@ 25
°
F
NORMAL CLOSED
HOT GAS DEFROST
SOLENOID
DEFROST CYCLE:
1) AFTER 220 MINUTES:
1) AFTER 220 MINUTES:
• A2 OPENS.
• B1 CLOSES.
• HOT GAS VALVE OPENS.
• ON DELAY RELAY CONTACT
CLOSES 1 TO 2, IN 3 MINUTES.
CLOSES 1 TO 2, IN 3 MINUTES.
• THERMOSTAT IS BYPASSED.
• COMPRESSOR RESTARTS AFTER
3 MINUTES FOR HOT GAS DEFROST.
3 MINUTES FOR HOT GAS DEFROST.
2) LIMIT SWITCH OPENS AT 40
°
F:
• COMPRESSOR POWER OFF.
• HOT GAS REMAINS ENERGIZED.
3) AFTER 20 MINUTES:
• B1 OPENS.
• HOT GAS VALVE IS DE-ENERGIZED.
• A2 CLOSES.
• COMPRESSOR STARTS THROUGH
TEMPERATURE
TEMPERATURE
CONTROL.
A2 RED
RED
TEMPERATURE
CONTROL
WHITE
WHITE
INTERNAL
CONNECTIONS
BLA
CK
BLA
CK
B (PO
WER)
S.P.S.T. MOMENTARY
CONTACT DEFROST SWITCH
W/ INDICATOR LIGHT
ON DELAY
RELAY
T15
T14
B1
B2
A
A2
A1
T11 T12 T13
1
S.S. TIMER
RELA
Y
RELA
Y
3
3
3
2
2
2
1
6
5
4
4
W
B
TO CONDENSING
UNIT