Hoshizaki MWH KM-515MAH 사용자 설명서

다운로드
페이지 94
45
2. "G" Control Board 
At startup, a 5-second delay occurs while the control board conducts an internal timer 
check. A beep occurs when the control switch is moved to the "ICE" position. The red 
"POWER OK" LED indicates proper control voltage and remains on unless a control 
voltage problem occurs. The green LEDs 1 through 4 energize and sequence from 
initial startup as listed in the table below. Note that the order of the LEDs from the 
outer edge of the control board is 1, 4, 3, 2. 
Sequence Step
LED
Energized
Components
Time LEDs are On 
Min.
Max.
Avg.
1-Minute Fill Cycle
4
WV
1 minute
Harvest Cycle
1, 4, 2
Comp, FMR, HGV, WV
2 minutes
20 minutes 3 to 5 minutes
Harvest Pump Timer
1, 3, 2
Comp, FMR, HGV, PM
0 seconds 50 seconds harvest pump timer 
setting
Freeze Cycle
1
Comp, FM/FMR, PM,
LLV
5 minutes
freeze timer
setting
30 to 35 minutes
Pump-Out Cycle
1, 4*, 3, 2 Comp, FMR, HGV, PM, 
WV* 
10 seconds 20 seconds *pump-out timer 
setting
The built-in safeties shut down the icemaker and have alarms as listed below.
No. of Beeps 
(every 3 sec.)
Type of Alarm
Notes
1
High Evaporator Temp.  
(temperature > 127°F) (53°C)
Check for harvest problem (stuck HGV or relay), hot 
water entering icemaker, or shorted thermistor. 
2
Harvest Backup Timer 
(harvest > 20 min. for two 
cycles in a row)
Check for open thermistor, HGV not opening, TXV or 
LLV leaking by, low charge, or inefficient Comp, or WRV 
leaking by.
3
Freeze Timer 
(freeze > freeze timer setting 
for two cycles in a row)
Check for FS stuck closed (up), WV leaking by, HGV 
leaking by, PM not pumping, TXV not feeding properly, 
LLV not opening, low charge, HM not bypassing, or 
inefficient Comp.
To reset the above safeties, press the "ALARM RESET" button with the power supply on.
6
Low Voltage 
(92Vac±5% or less)
Red LED turns off if voltage protection operates.  
The control voltage safeties automatically reset when 
voltage is corrected.
7
High Voltage 
(147Vac±5% or more)
Legend: 
Comp–compressor; FM–fan motor; FMR–fan motor remote; FS–float switch;  
HGV–hot gas valve; HM–headmaster (C.P.R.); LLV–liquid line valve; PM–pump 
motor; 
TXV–thermostatic expansion valve; WRV–water regulating valve;  
WV–inlet water valve