9. ADJUSTMENT OF WATER REGULATING VALVE - WATER-COOLED
MODEL ONLY
The Water Regulating Valve (also called “WATER REGULATOR”) is factory-adjusted. No
adjustment is required under normal use. Adjust the Water Regulator, if necessary, using the
following procedures.
adjustment is required under normal use. Adjust the Water Regulator, if necessary, using the
following procedures.
1) Attach a pressure gauge to the high-side line of the system. Or prepare a thermometer to
check for the condenser drain temperature.
check for the condenser drain temperature.
2) Rotate the adjustment screw by using a flat blade screwdriver, so that the pressure gauge
shows 270 PSIG or the thermometer reads 104–115° F, 5 minutes after a freeze cycle or
icemaking process starts. When the pressure exceeds 270 PSIG, or the condenser drain
temperature exceeds 115° F, rotate the adjustment screw counterclockwise. See Fig. 1.
shows 270 PSIG or the thermometer reads 104–115° F, 5 minutes after a freeze cycle or
icemaking process starts. When the pressure exceeds 270 PSIG, or the condenser drain
temperature exceeds 115° F, rotate the adjustment screw counterclockwise. See Fig. 1.
3) Check that the pressure or the condenser drain temperature holds a stable setting.
Fig. 1