Proper installation/ducting is extremely
important to ensure maximum
performance. Use a qualified and
trained installer.
DUCTING
• Check with a qualified and
trained installer or local codes
for makeup air requirements, 
if any.
• Max. duct run 
o For 300 – 1,200 CFM—50’
(152.4 m)
o For 1,500 CFM—75’ (22.9 m)
o Duct run length is for general
reference only; for longer
duct runs, increase duct size
and contact a qualified and
trained installer.
o Straight runs and gradual
turns are best; for example,
each 90° elbow is equivalent
to 5’ – 10’ (1.52 – 3.05 cm) of
straight run.
• 7” (17.8 cm) round duct for
300 – 600 CFM; 10” for 900 –
1500 CFM
o Never use flexible duct; it
creates back pressure/air
turbulence and greatly
reduces performance.
GAS
Not applicable
ELECTRICAL
• Hardwire direct with two-wire
with ground
• 120 VAC/60 Hz 
• Max. amp usage (rating
includes rec. ventilator kit
rating) 
PLUMBING
Not applicable
P L A N N I N G   A N D   D E S I G N   G U I D E
V I K I N G R A N G E . C O M       •       1 - 8 8 8 - V I K I N G 1
R E L E A S E D 1 2 / 1 / 0 7
© 2 0 0 7   V R C — INFORMATION SUBJECT TO CHANGE 
VENTILATION
Built-In Island/Classic Chimney Island Hood
Installation Requirements
* A 1,200 CFM interior- or exterior-power ventilator should be used when installed over range/rangetop with gas char-grill.
** It is recommended that the 1,500 CFM ventilator be used with longer duct runs.
Note: Maximum amp rating for hoods includes recommended ventilator kit rating. All products must be hard wired with two-wire ground. An interior- or
exterior-power ventilator kit must be purchased for installation with all 18”H. hoods.
Model
Ventilator Kits
Duct Size
Max. Amps   
Interior
Exterior
Interior
Exterior
Interior
Exterior
VIH3608
VIV600/1200*
VEV900/1200*
7” (17.8 cm)/
10” (25.4 cm)
4.9/7.4
7.4/4.7
10” (25.4 cm)
VIH4208
VIV600/1200*
VEV900/1200/1500*
7” (17.8 cm)/
10” (25.4 cm)
4.9/7.4
7.4/4.7/5.5
10” (25.4 cm)
VIH5408
VIV1200*
VEV1200/1500**
10” (25.4 cm)
10” (25.4 cm)
8.2
5.5/6.2
VIH6608
VIV1200*
VEV1200/1500**
10” (25.4 cm)
10” (25.4 cm)
8.2
5.5/6.2
VCIH3608
DIV600*
DEV900/1200*
7” (17.8 cm)
10” (25.4 cm)
3.9
6.6/3.9
VCIH4208
DIV600*
DEV900/1200/1500*
7” (17.8 cm)
10” (25.4 cm)
4.7
7.4/4.8/5.5
VCIH5408
DIV1200*
DEV1200/1500**
10” (25.4 cm)
10” (25.4 cm)
8.6
5.6/6.4
VCIH6608
DIV1200*
DEV1200/1500**
10” (25.4 cm)
10” (25.4 cm)
9.5
6.5/7.3
DCIH3604
DIV600
DEV900/DEV1200*
7” (17.8 cm)
10” (25.4 cm)
4.7
8.6
DCIH4204
DIV600
DEV1200/DEV1500**
7” (17.8 cm)
10” (25.4 cm)
4.7
7.4/4.7/5.5
DCIH5404
DIV1200*
DEV1200/DEV1500**
10” (25.4 cm)
10” (25.4 cm)
8.6
5.6/6.4
Note: All CFMs are based on tests with 0.1 static pressure. Without applying static pressure (some brands do not), CFM could be
greatly overstated.