LDVT Series Direct Vent GaS Fireplace
10007852
FP1012
Top vent max run
1/25/00 djt
20' (6m)
7.5' (2.3m)
Pipe Straps
Every 3’ (914mm)
Firestop/Zero
Clearance Sleeve
Pipe
Straps Every
3’ (914mm)
FP1012
Fig. 14 Support straps for horizontal runs.
•
If a 90° elbow is used in the horizontal vent run
(level height maintained) the maximum horizontal
vent length is reduced by 36” (914mm). This does
not apply if the 90° elbows are used to increase or
redirect a vertical rise.
(level height maintained) the maximum horizontal
vent length is reduced by 36” (914mm). This does
not apply if the 90° elbows are used to increase or
redirect a vertical rise.
Example: According to the chart the maximum
horizontal vent length in a system with a 7.5’ (2.3 m)
vertical rise is 20’ (6m) and if a 90° is required in the
horizontal vent it must be reduced to 17’ (5.2 m).
vertical rise is 20’ (6m) and if a 90° is required in the
horizontal vent it must be reduced to 17’ (5.2 m).
In Figure 16, Dimension A plus B must not be
greater than 17’ (5.2 m).
Horizontal plane means no vertical rise exists on this
portion of the vent assembly.
portion of the vent assembly.
•
The maximum number of 90° elbows per side wall
installations is three (3).
installations is three (3).
•
If a 90° elbow is fitted directly onto the fireplace
flange the maximum horizontal vent run before the
termination or a vertical rise is 36” (914mm).
flange the maximum horizontal vent run before the
termination or a vertical rise is 36” (914mm).
3'
(914mm)
FP1237
horizontal plane
12/02
FP1237
Fig. 15 Maximum horizontal vent run.
7.5'
(2.3m)
A
B
A + B = 17' (5.2m) Max.
1 x 90° elbow in horizontal plane = 3’ (914mm)
FP1238
Fig. 16 Maximum vent run with elbows.
•
The maximum number of 45° elbows permitted per
side wall installation is two (2). These elbows can be
installed in either the vertical or horizontal run.
side wall installation is two (2). These elbows can be
installed in either the vertical or horizontal run.
•
For each 45° elbow installed in the horizontal run,
the length of the horizontal run MUST be reduced by
18” (457 mm). This does not apply if the 45° elbows
are installed on the vertical part of the vent system.
the length of the horizontal run MUST be reduced by
18” (457 mm). This does not apply if the 45° elbows
are installed on the vertical part of the vent system.
•
The maximum number of elbow degrees in a system
is 270°. (Fig. 17)
is 270°. (Fig. 17)
Example:
Elbow 1 = 90°
Elbow 2 = 45°
Elbow 3 = 45°
Elbow 4 = 90°
Total angular variation = 270°
1 + 2 + 3 + 4 = 270°
FP1239
Fig. 17 Maximum number of elbow degrees.
1
2
3
4